6 Parameters
6 - 102
E5@C-T Digital Temperature Controllers User’s Manual (H185)
pmvd
Direct Setting of Position
Proportional MV
Close control must be used (Position-proportional
Model).
• The Direct Setting of Position Proportional MV parameter can be set to ON to enable
specifying the valve open with the MV at Stop, MV at PV Error, and Manual MV
parameters.
z Related Parameters
MV at Reset and MV at Error (Adjustment Level): Page 6-39
PV/MV (Manual MV) (Manual Control Level): Page 6-53
pvrp
PV Rate of Change Calculation
Period
Alarms 1, 2, 3, and 4 must be assigned. The alarm
type must be set to 13.
• The change width can be found for PV input values in any set period. Differences with
previous values in each set period are calculated, and an alarm is output if the results
exceed the alarm value.
• The PV rate of change calculation period can be set in units of 50 ms (sampling period).
z Related Parameters
Process Value/Set Point (Operation Level): Page 6-8
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
Function
Setting
Setting range Default
on: Enabled, off: Disabled off
See
See
Function
Setting
Setting range Unit Default
1 to 999 Sampling cycle 20 (1 s)
See
See