4 Basic Operation
4 - 12
E5@C-T Digital Temperature Controllers User’s Manual (H185)
Operating Flow for Step Time Programming
Item Operating flow Settings Page
Turn ON the power supply and then press the O Key
for at least three seconds to move to the Initial Setting
Level.
4-3
1
Make the
initial
settings
other
than
program-
related
settings.
Set the parameter to a K thermocouple (default). 4-18
Set the parameter to PID control (default). 4-21
Set the parameter to an upper-limit alarm (default). 4-56
2
Make the
initial
pro-
gram-rel
ated set-
tings.
Set the parameter to hours and minutes (default). 4-33
Set the parameter to step time programming (default). 4-34
Set the parameter to stop control (default). 4-35
Set the parameter to continue operation (default). 4-36
Set the parameter to reset status (default). 4-38
Set the parameter to the program SP (default). 4-38
Power ON
Set the Input Type parameter.
Set the Alarm Type parameter.
Initial Setting Level
Set the PID ON/OFF parameter.
Set the Program Time Unit parameter.
Initial Setting Level
Set the Startup Operation parameter.
Set the Operation End Operation parameter.
Set the Reset Operation parameter.
Set the Step Time/Rate of Rise Programming parameter.
Set the SP Mode parameter.
Adjustment Level

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals