Operation Level Section 5-3
This parameter is set to one of the input values “X” in the alarm type list.
• This parameter sets the alarm value for alarm 2.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the Decimal
Point parameter setting.
• The set value is saved in the Alarm 2 parameter in the current bank.
■ Related Parameters
Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point
(initial setting level): Page 226 (initial setting level)
Alarm 2 type (initial setting level): Page 233
Standby sequence reset: Page 244, Auxiliary output * open in alarm: Page
245, Alarm 2 hysteresis: Page 233, Alarm 2 latch: Page 250 (advanced func-
tion setting level)
Bank * alarm value 2 (bank setting level): Page 212
This parameter is set to one of the input values “X” in the alarm type list.
• This parameter sets the alarm value for alarm 3.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the Decimal
Point parameter setting.
• The set value is saved in the Alarm 3 parameter in the current bank.
■ Related Parameters
Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point
(initial setting level): Page 226 (initial setting level)
Alarm 3 type (initial setting level): Page 234
Standby sequence reset: Page 244, Auxiliary output * open in alarm: Page
245, Alarm 3 hysteresis: Page 233, Alarm 3 latch: Page 250 (advanced func-
tion setting level)
Bank * alarm value 3 (bank setting level): Page 213
al-2 Alarm Value 2
Alarm 2 must be assigned.
The alarm 2 type must not be 0, 1, 4,
5, or 12.
Setting range Unit Default
−1999 to 9999 EU 0
Function
Setting
See
See
al-3 Alarm Value 3
Alarm 3 must be assigned.
The alarm 3 type must not be 0, 1, 4,
5, or 12.
Setting range Unit Default
−1999 to 9999 EU 0
Function
Setting
See
See