8.11 Control initial setting 2 level (l.2)
8-49
Setting data
• These settings can only be used for outputs selected for transfer
output using output assignment.
*1 Will be initialized if the input type, temperature units, scaling display
value, SP upper- and lower-limit, or applicable control/transfer
output assignment is changed.
● Related information
"5.8 Using transfer output" (P.5-32)
● Related setting data
"Input
∗ type" (Input initial setting level) (P.8-36)
"Control/Transfer output
∗ assignment" (Control initial setting 2 level)
(P.8-46)
Transfer output
∗ upper limit
Transfer output
∗ lower limit
(
∗: 1 to 4)
trh. ∗
trl. ∗
Transfer output using output assignment
l.2
Function
Setting
Control/
Transfer output
assignment
data
Setting range
Default value
(upper limit/
lower limit of
transfer
output) *1
Decimal
point
position
units
SP
SP lower limit to
SP upper limit
1300.0/-200.0
Depends on
input type
EU
Ramp SP
SP lower limit to
SP upper limit
1300.0/-200.0
Depends on
input type
EU
PV
Lower limit of
sensor setting
range to upper
limit of sensor
setting range
(temperature)
Upper- and
lower-limit of
sensor setting
range
Depends on
input type
EU
-19999 to 99999
(analog)
Scaling display
value 2/1
Depends on
input type
EU
Control output
(heating or
open)
Standard: -5.0 to
105.0; Heating/
cooling: 0.0 to
105.0
100.0/0.0 1 %
Control output
(cooling or
close)
0.0 to 105.0 100.0/0.0 1 %
Valve opening -10.0 to 110.0 100.0/0.0 1 %
Reference
Reference