Section 2 Preparations
2-14
Preparations
Relay output specifications are as follows:
250 V AC 1 A
On the E5ER-@T@@ auxiliary outputs 1 and 2 (SUB1 and 2) output
to terminals D3 to D6.
Transistor output specifications are as follows:
Max. load voltage 30 V DC
Max. load current 50 mA
Residual voltage 1.5 V max.
Leakage current 0.4 mA max.
Potentiometer
inputs (terminals)
If you wish to use a position proportional control type to monitor the
amount of valve opening or perform closed control, connect a poten-
tiometer (PMTR) as shown in the following.
For information on the potentiometer, see the manual for the valve
you are connecting. Terminal number meanings are as follows.
O:OPEN, W:WIPE, C:CLOSE
The input range is 100
to 2.5 k (Between C to O).
SUB2
E5ER-@T@@
3
4
5
6
SUB1
D
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
ABCDE
FGHI J K
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
AB
CDE
E5AR
E5ER
PMTR
PMTR
1
2
3
O
W
C
1
2
3
O
W
C
E5AR E5ER
K E

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AR - MANUAL 2 and is the answer not in the manual?

Omron E5AR - MANUAL 2 Specifications

General IconGeneral
BrandOmron
ModelE5AR - MANUAL 2
CategoryController
LanguageEnglish

Related product manuals