2.2 How to Use the Terminals
2-13
Preparations
• Control outputs that are not used for control can be used for transfer
output with the "control output / transfer output assignment" setting.
• Specifications for each output type are as follows:
* The value for the E5AR-QQ@@@WW-@@@ is 21 mA max.
• The position proportional type has relay outputs (250 V AC, 1 A).
Control output 1 (OUT1) is open output and control output 2 (OUT2)
is closed output.
• Relay output specifications are as follows:
250 V AC, 1 A (including inrush current)
● Auxiliary outputs
(terminals)
•On the E5AR-@4@@, auxiliary outputs 1 to 4 (SUB1 to 4) output to
terminals B1 to B6.
•On the E5ER-@4@@, auxiliary outputs 1 to 4 (SUB1 to 4) output to
terminals B1 to B6. On the E5ER-@T@@ , auxiliary outputs 1 to 2
(SUB1 to 2) output to terminals D3 to D6.
Output type Specifications
Pulse voltage
output
Output voltage: 12 V DC+15%, –20%(PNP)
Max. load current: 40mA*, with short-circuit
protection circuit
Linear current
output
0-20 mA DC (resolution: approx. 54,000)
4-20 mA DC (resolution: approx. 43,000)
Load: 500
Ω max.
E5AR
OUT2
(Closed side output)
OUT1
(Open side output)
3
4
5
6
E5ER
OUT2
(Closed side output)
OUT1
(Open side output)
3
4
5
6
F C
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
ABCDE
FGHI J K
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
AB
CDE
E5AR
E5ER
COM
SUB1
SUB2
COM
SUB3
SUB4
COM
SUB1
SUB2
COM
SUB3
SUB4
SUB1
SUB2
SUB3
SUB4
E5AR
3
2
1
4
5
6
SUB1
SUB2
B
SUB3
SUB4
E5ER-@4@@
3
2
1
4
5
6
SUB1
SUB2
B