246
Appendix A
Monitoring Test Output Terminals: NE1A-SCPU01-V1
Explicit
message
Service Function Command Response
Service
code
Class
ID
In-
stance
ID
At-
tribute
ID
Data size
Monitor Mode for
Terminal Mainte-
nance Information
Read Reads the monitor mode of
maintenance information of the
test output (1 to 4) specified by
the Instance ID.
0E hex 307
hex
01 to 04
hex
83 hex --- 1 byte
00 hex: Total ON time
mode
01 hex: Contact opera-
tion counter
mode
Write Writes the monitor mode of
maintenance information of the
test output (1 to 4) specified by
the Instance ID.
10 hex 307
hex
01 to 04
hex
83 hex 1 byte
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
---
SV for Test Output
Total ON Time or
Contact Operation
Counter
Read Reads the SV of the total ON
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the input (1 to 4) spec-
ified by the Instance ID.
0E hex 307
hex
01 to 04
hex
86 hex --- 4 bytes
0000 0000 to FFFF
FFFF hex
(0 to 4,294,967,295)
Write Writes the SV of the total ON
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the input (1 to 4)
specified by the Instance ID.
10 hex 307
hex
01 to 04
hex
86 hex 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
---
Read Test Output
Total ON Time or
Contact Operation
Counter
Read Reads the total ON time (unit:
seconds) or contact operation
counter (unit: operations) for
the input (1 to 16) specified by
the Instance ID.
0E hex 307
hex
01 to 04
hex
84 hex --- 4 bytes
0000 0000 to FFFF
FFFF hex
(0 to 4,294,967,295)
Reset Test Output
Total ON Time or
Contact Operation
Counter
Reset Resets to 0 the total ON time
(unit: seconds) or contact
operation counter (unit: opera-
tions) for the test output (1 to 4)
specified by the Instance ID.
05 hex 307
hex
01 to 04
hex
84 hex --- ---
Read Monitor
Status of Test
Output Total ON
Time or Contact
Operation Counter
Read Reads the monitor status of the
total ON time or contact opera-
tion counter of the test output (1
to 4) specified by the Instance
ID.
0E hex 307
hex
01 to 04
hex
85 hex --- 1 byte
00 hex: In range
01 hex: Out of range
(over monitor
value)
Read Test Output
Safety Flag
Read Reads the normal flag status
for the test output (1 to 4)
specified by the Instance ID.
0E hex 307
hex
01 to 04
hex
68 hex --- 1 byte
00 hex: Normal
01 hex: Error
Read Test Output
Error Information
Cause
Read Reads the cause for the normal
flag of the test output (1 to 4)
specified by the Instance ID
being OFF (error).
0E hex 307
hex
01 to 04
hex
76 hex --- 1 byte
00 hex: No error
01 hex: Invalid
configuration
02 hex: Overcurrent
detection
05 hex: High constant
error
06 hex: Undercurrent
detection
Read OR of Test
Output Safety Flags
Read Reads the logical OR of the
normal flag status for all test
outputs 1 to 4.
0E hex 308
hex
01 hex 69 hex --- 1 byte
00 hex: All normal
01 hex: Error
Read OR of
Monitor Status of
Test Output Total
ON Times or
Contact Operation
Counters
Read Reads the logical OR of the
monitor status of the total ON
time or contact operation
counter for all test outputs 1 to
4.
0E hex 308
hex
01 hex 72 hex --- 1 byte
00 hex: All in range
01 hex: Test output out
of range (over
monitor value)