EasyManua.ls Logo

Omron NE1A Series - Page 246

Omron NE1A Series
258 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
247
Appendix A
A-3-2 Explicit Messages: NE1A-SCPU02
Reading General Status: NE1A-SCPU02
Reading I/O Area: NE1A-SCPU02
Explicit
message
Service Function Command Response
Service
code
Class
ID
In-
stance
ID
At-
tribute
ID
Data size
Read Unit General
Status
Read Reads the Unit’s general
status.
0E hex 39 hex 01 hex
6E hex --- 1 byte
Explicit
message
Service Function Command Response
Service
code
Class
ID
In-
stance
ID
At-
tribute
ID
Data size
Read I/O Area Read Reads the Unit’s I/O data.
Instance ID Specification
Range:
Local input = 01
Local output/test output = 02
Safety input = 05
Safety output = 06
Address Specification Range:
Local input: 0 to 4
Local output/test output: 0 or 1
Safety input: 0 to 511
Safety output: 0 to 511
4B hex 306
hex
01, 02,
05, and
06 hex
--- First and second
byte offset
address:
0000 to 01FF
hex (0 to 511),
Third and fourth
byte read size:
0001 to 0100
hex (1 to 256)
Read data

Table of Contents