13-11
13 Communications Performance and Communications Load
NJ-series CPU Unit Built-in EtherNet/IP Port Users Manual (W506)
13-2 Adjusting the Communications Load
13
13-2-4 Changing the RPI
3
The usage of capacity without multicast filtering can be adjusted against the tag data link’s
allowable bandwith by changing the associated devices’ packet interval (RPI) settings.
The RPI settings can be changed with the following three methods.
Method 1:
Change All Connections to the Same RPI
The usage of capacity without a multicast filter can be adjusted for all devices by changing the
packet intervals (RPI) settings for all of the device’s connections to the same RPI at the same
time.
(1) Click the Set Packet Interval (RPI) Button at the bottom of the Usage of Device Bandwidth
Dialog Box.
(2) The Set Packet Interval (RPI) Dialog Box will be displayed. Input a new RPI value, and click
the OK Button.