14-17
14 Troubleshooting
NJ-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
14-2 Troubleshooting
14
14-2-2 Error Descriptions
Event name EtherNet/IP Processing Error Event code 14220000 hex
Meaning A fatal error was detected in the EtherNet/IP Function Module.
Source EtherNet/IP Function Module Source details Communications
port
Detection
timing
Continuously
Error attributes Level Partial fault Recovery Cycle the power
supply.
Log category System
Effects User program Continues. Operation EtherNet/IP communications will not operate.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
OFF Lights. ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
Hardware has failed. Replace the CPU Unit. None
Attached
information
None
Precautions/
Remarks
None
Event name Basic Ethernet Setting Error Event code 34210000 hex
Meaning An error was detected in the Ethernet settings.
Source EtherNet/IP Function Module Source details Communications
port
Detection
timing
At power ON or
Controller reset
Error attributes Level Partial fault Recovery Automatic recov-
ery, cycle the
power supply, or
reset Controller
Log category System
Effects User program Continues. Operation EtherNet/IP communications will not operate.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
OFF Flashes at 1-s intervals. ---
System-defined
variables
Variable Data type Name
_EIP_EtnCfgErr BOOL Basic Ethernet Setting Error
Cause and
correction
Assumed cause Correction Prevention
Power was interrupted when a down-
load was in progress for the Ethernet
basic settings.
Cycle the power supply to the Con-
troller or reset the Controller. If normal
operation is restored by cycling the
power supply to the Controller or
resetting the Controller, a memory
error has occurred and may occur
again. Replace the CPU Unit. If oper-
ation is not restored even after you
cycle the power supply or reset the
Controller, perform either of the fol-
lowing operations and download the
settings again.
• Perform a Memory All Clear opera-
tion.
• Identify the cause of error from
those listed in the event log details
and correct the settings.
If operation is not recovered by the
above, replace the CPU Unit.
Do not turn OFF the power supply to
the Controller while a download is in
progress for the Ethernet basic set-
tings.
Memory error None
Attached
information
Attached information 1: Type of errors (01 hex: Non-volatile memory access error, 02 hex: Inconsistency in settings)
Attached information 2: Error details
(00 hex: Non-volatile memory access error, 11 hex: Incorrect baud rate setting, 12 hex: Unsupported baud rate)
Precautions/
Remarks
The cause of error can be identified with the attached information.