14   Troubleshooting
14-18
NJ-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Event name TCP/IP Basic Setting Error (Local Port IP Address) Event code 34220000 hex
Meaning An error was detected in the IP address settings.
Source EtherNet/IP Function Module Source details Communications 
port
Detection 
timing
At power ON or 
Controller reset
Error attributes Level Partial fault Recovery Automatic recov-
ery (after down-
loading the 
settings), cycle 
the power sup-
ply, or reset Con-
troller
Log category System
Effects User program Continues. Operation EtherNet/IP communications will not operate.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
OFF Flashes at 1-s intervals. ---
System-defined 
variables
Variable Data type Name
_EIP_IPAdrCfgErr BOOL Basic TCP/IP Setting Error
Cause and 
correction
Assumed cause Correction Prevention
Power was interrupted when a down-
load was in progress for the TCP/IP 
basic settings.
Cycle the power supply to the Con-
troller or reset the Controller. If normal 
operation is restored by cycling the 
power supply to the Controller or 
resetting the Controller, a memory 
error has occurred and may occur 
again. Replace the CPU Unit. If oper-
ation is not restored even after you 
cycle the power supply or reset the 
Controller, perform either of the fol-
lowing operations and download the 
settings again.
• Memory All Clear operation.
• Identify the cause of error from 
those listed in the event log details 
and correct the settings.
If operation is not recovered by the 
above, replace the CPU Unit.
Do not turn OFF the power supply to 
the Controller while a download is in 
progress for the TCP/IP basic set-
tings.
Memory error None
The IP address acquired from 
BOOTP server is illegal.
Correct the IP address that was pro-
vided to this port by the BOOTP 
server so that it is within the range 
specified for an NJ-series Controller.
Correct the IP address that was pro-
vided to this port by the BOOTP 
server so that it is within the range 
specified for an NJ-series Controller.
Attached 
information
Attached information 1: Type of errors (01 hex: Non-volatile memory access error, 02 hex: Inconsistency in settings)
Attached information 2: Error details (01 hex: Non-volatile memory access error
When settings are inconsistent (11 hex: Illegal IP address, 12 hex: Illegal subnet mask, 13 hex: Illegal default gateway, 
14 hex: Illegal priority DNS, 15 hex: Illegal exchange DNS, 16 hex: Illegal domain name)
Precautions/
Remarks
The cause of error can be identified with the attached information.