14-2-2 Error Descriptions
Event name Link OFF Detected Event code 84060000 hex
Meaning The Ethernet link status turned OFF.
Source EtherNet/IP Function Module Source details Communications
port
Detection
timing
After link is
established
Error attributes Level Observation Recovery --- Log category System
Effects User program Continues. Operation EtherNet/IP communications will not operate.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
--- --- OFF
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
An Ethernet cable is broken, discon-
nected, or loose.
Connect the Ethernet cable securely.
If the cable is broken, replace it.
Connect the Ethernet cable securely.
Check the cable to make sure that it is
not disconnected.
The Ethernet switch power supply is
turned OFF.
Turn ON the power supply to the
Ethernet switch. Replace the Ethernet
switch if it fails.
Do not turn OFF the power supply to
the Ethernet switch.
Baud rate mismatch. Correct the settings so that the same
baud rate is used as for the remote
communications nodes.
Set the same baud rate as for the
remote communications nodes.
Noise Implement noise countermeasures if
there is excessive noise.
Implement noise countermeasures.
One of the following operations was
performed.
• The Identify object was reset.
• Settings were downloaded from the
Network Configurator and Ether-
Net/IP was restarted.
• Settings for EtherNet/IP were down-
loaded from the Sysmac Studio or
the Memory All Clear operation was
performed.
None
This error occurs when the operations
on the left are preformed.
None
This error occurs when the operations
on the left are preformed.
Attached
information
None
Precautions/
Remarks
None
Event name Tag Data Link Download Started Event code 94010000 hex
Meaning Changing the tag data link settings started.
Source EtherNet/IP Function Module Source details CIP Detection
timing
At user operation
Error attributes Level Information Recovery --- Log category Access
Effects User program Continues. Operation Not affected.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
Flashes at 1-s intervals. --- ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
Changing the tag data link settings
started.
--- ---
Attached
information
Attached information 1: Controller status (01 hex: PROGRAM mode, 02 hex: RUN mode)