4-3 High-speed 1:N NT Link
 
4-3-1  Unit Setting Methods 
The methods for setting each Unit are as follows: 
 
Connecting to CS-series CPU Units  
CS-series CPU Units: 
CS1G/H-CPU@@-EV1/CS1G/H-CPU@@H 
 
PLC Setup Area 
• Using RS-232C 
When connecting the PT to a CS-series CPU Unit, set the communications conditions in the 
PLC Setup according to the communications port used, as follows: 
 
Using Built-in RS-232C Port of CS1G/H or CS1G/H-H  
Address   Write value Settings 
160  8200  1:N NT Link Mode 
161  000A  Baud rate (high-speed) 
166 
000@  @: Largest unit number (1 to 7) of connected PTs. (See note.) 
Note:  To connect a single Unit in a 1:N connection, set the value for @ to 1 or higher.  
 
For example, to connect PTs with unit numbers 0, and 2 to 5 to the built-in RS-232C port in 
high-speed 1:N NT Links, set address 160 to 8200 Hex, address 161 to 000A Hex, and ad-
dress 166 to 0005 Hex. 
Set whether the PLC Setup is set directly from the Programming Device (Programming Con-
sole) or created by the Support Software (CX-Programmer) and transferred to the CPU Unit. 
Refer to the SYSMAC CS/CJ Series Operation Manual (W339) for information on the PLC 
Setup. 
 
Reference
  To set high-speed 1:N NT Link communications from the CX-Programmer, set the baud 
rate to 115,200 bps.  
 
4-17