Appendix 3 Using NS-AL002 Converters
 
 
A-3-2  Mounting and Removing  
Connect the NS-AL002 directly to port A or port B of the PT. Two NS-AL002 Adapters 
cannot be connected to ports A and B simultaneously. 
Mount the Adapter by tightening and securing the mounting screws on both of the D-Sub 
connectors. The correct tightening torque is 0.3 N
•m. The correct tightening torque for the 
terminal block is 0.5 N
•m. 
To remove the Adapter, loosen the screws and pull out the Adapter. 
 
Note
  •  Always turn OFF the power to the PT before removing the Adapter. 
  •  Do not touch the surface or the mounted parts of the Board with bare hands. 
Always discharge any static electricity from your body before handling the Board. 
  •  Mount to the PT after securely connecting the cable to the terminal block. 
 Be sure to tighten the mounting screws on both of the D-Sub connectors. If the screws 
are loose, the FG terminals of the PT and NS-AL002 will not be connected. 
 
A-3-3 Specifications  
The following table shows the general specifications and communications specifications of 
the Adapter. 
 
● General Specifications  
Item   Specifications  
Dimensions   45 × 49 × 28.5 mm (W × H × D)  
Weight   50 g max. 
Ambient operating temperature  0 to 50°C 
Storage temperature   −20 to 60°C 
Ambient operating humidity   35% to 85% (without condensation)  
Rated power supply   5 V ±10% (through pin 6 of the RS-232C connector)  
Power consumption   150 mW max.  
Operating environment   No corrosive gases.  
Vibration resistance   Conforms to PT specifications.  
Shock resistance   Conforms to PT specifications.  
 
 
Reference
  NS-series RS-485 (two-wire) communications are used to connect to an OMRON 
Temperature Controller. The NS-AL002 cannot be used with the NT-series PTs or 
PLCs.  
 
● Communications Specifications  
• RS-422A Interface  
Item   Specifications  
Baud rate   115.2 kbps max.  
Transmission distance   500 m total length (See note 1.) 
Terminal block format   8-terminal terminal block, M3.0 
Insulation  No insulation (See note 2.) 
Note 1:  This specification is for a configuration in which all the Adapters connected on the same 
transmission path are NT-AL002 Link Adapters. If a CJ1W-CIF11 Conversion Adapter is 
used, the total length is 50 m. 
Note 2:  The RS-422A and RS-232C are not insulated.  
A-18