6 - 21
6 Analog Input Units
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
6-5 Function
6
6-5-3 Moving Average
This section describes how to configure settings with the Sysmac Studio.
When you are using Support Software other than the Sysmac Studio, in the Edit Unit Operation Set-
tings Tab Page, set the parameters described in the procedure and transfer the settings to the target
NX Unit.
For details on how to display the Edit Unit Operation Settings Tab Page and to transfer settings to an
NX Unit with Support Software other than the Sysmac Studio, refer to the operation manual for the Sup-
port Software that you are using.
1 Display the Edit Unit Operation Settings Tab Page.
For the display methods, refer to A-7 Displaying the Edit Unit Operation Settings Tab Page on
page A-61
.
2 Enter the time to process moving average (0 to 32000 or 0 to 640 μs) in the text box of Input
Moving Average Time for the channel you want to set.
Setting Method