EasyManua.ls Logo

Omron OMNUC G5 R88D-KT50F - Page 566

Omron OMNUC G5 R88D-KT50F
632 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-7
11-3 Alarm List
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
11
Troubleshooting and Maintenance
26
0
Overspeed
The motor rotation speed exceeded the value
set on the Overspeed Level set (Pn513).
√√√
1
Overspeed 2
The motor rotation speed exceeded the value
set on the Overspeed Level set 2 (Pn615).
√√−
27
0
Command pulse
frequency error
A command pulse frequency error was
detected.
√√√
2
Command pulse multiplier
error
The command pulse divider or
multiplier is not suitable.
√√√
28 0
Pulse regeneration error The pulse regeneration output
frequency exceeded the limit.
√√√
29 0
Error counter overflow Error counter value based on the
encoder pulse reference exceeded
2
29
(536,870,912).
√√−
30
(st)
0
Safety input error Safety input signal turned OFF.
−√−
33
0
Interface input duplicate
allocation error 1
A duplicate setting for the interface
input signals was detected.
√−−
1
Interface input duplicate
allocation error 2
√−−
2
Interface input function
number error 1
An undefined number was detected in
the interface input signal allocations.
√−−
3
Interface input function
number error 2
√−−
4
Interface output function
number error 1
An undefined number was detected in
the interface output signal allocations.
√−−
5
Interface output function
number error 2
√−−
6
Counter reset allocation
error
The counter reset function was allocated
to something other than input signal SI7.
√−−
7
Command pulse
prohibition input allocation
error
The command pulse prohibition input
function was allocated to something
other than input signal SI10.
√−−
34 0
Overrun limit error The motor exceeded the allowable
operating range set in the Overrun
Limit Setting (Pn514) with respect to
the position command input.
√√−
36
0 to
2
Parameter error
Data in the Parameter Save area was
corrupted when the power supply was turned
ON and data was read from the EEPROM.
−−−
37
0 to
2
Parameters destruction The checksum for the data read from
the EEPROM when the power supply
was turned ON does not match.
−−−
38 0
Drive prohibition input
error
The forward drive prohibition and reverse
drive prohibition inputs are both turned OFF.
−√−
Alarm
number
Error detection function
Detection details and probable
cause
Attribute
Main Sub
History
Can be
cleared
Immediate
stop *1