Startup Procedure and
Test Run
4
4.6 Auto-Tuning
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 145
Table 4.7 Input Data for Induction Motor Auto-Tuning
Input Data Unit
Auto-Tuning Mode
(Value of T1-01 [Auto-tuning Mode Selection])
Rotary Auto Tune
(0)
Static1 AutoTune
(1)
Static (R)
(2)
T1-02 [Motor Rated Power] kW × × ×
T1-03 [Motor Rated Voltage] V × × -
T1-04 [Motor Rated Current] A × × ×
T1-05 [Motor Base Frequency] Hz × × -
T1-06 [Motor Poles Number] - × × -
T1-07 [Motor Base Speed] rpm × × -
T1-08 [PG PulsePerRevolution] - ×
*1
×
*1
-
T1-09 [Motor NoLoad Current] A - × -
T1-10 [Motor Rated Slip Frequency]
Hz - ×
*2
-
T1-11 [Motor Iron Loss]
W ×
*3
- -
T1-12 [Test Mode Selection]
*4
- - ×
*5
-
T1-13 [No-load Voltage]
V ×
*6
×
*6
-
*1 Input this value when A1-02 = 3 [Control Method = CLVector].
*2 0 Hz is displayed as the initial value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0 Hz.
*3 Input this value when A1-02 = 0 or 1 [Control Method = V/f Control or PG V/f Control].
*4 If T1-12 = 1 [Test Mode Selection = Yes], when you run the motor in Drive Mode for the first time after Auto-Tuning, the drive will
automatically set E2-02 [Mot Rated Slip] and E2-03 [Mot No-Load Current].
*5 Input this value when T1-01 [Auto-tuning Mode Selection] = 0 Hz.
*6 Set the same value to No-Load Voltage as T1-03 [Motor Rated Voltage] to get the same characteristics using Yaskawa 1000-Series
drives or other legacy models.
Auto-Tuning for PM Motors
This section gives information about Auto-Tuning for PM motors. Set these parameters for Auto-Tuning:
Motor parameters E1-xx [E1: V/F PARAMETER MOTOR 1], E5-xx [E5: PM MOTOR SETTINGS]
Speed feedback detection uses F1-xx [F1: ENCODER] (only with PM CLVector)
Table 4.8 Auto-Tuning for PM Motors
Method Parameter Settings Applicable When/Advantages
Applicable Control Method
(Value of A1-02 [Control Method])
PM OLVector
(5)
PM AOLVector
(6)
PM CLVector
(7)
PM Motor Parameter Settings T2-01 = 0
When the information from the motor test report or
motor nameplate is not available.
Rotational/Stationary Auto-Tuning that energizes
the motor is not done. Manually input the necessary
motor parameters.
× × ×
PM Static Full AutoTune T2-01 = 1
When the information from the motor test report or
motor nameplate is not available.
Note:
With Stationary Auto-Tuning, the energized drive
stays stopped for approximately 1 minute. During
this time, the drive automatically measures the
necessary motor parameters.
× × ×
PM Static R Autotune T2-01 = 2
After Auto-Tuning, the wiring distance between the
drive and motor changed by 50 m or more.
When the motor output and drive capacity are
different.
× × ×

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals