11.6 E: MOTOR
418 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E5-04
(032C)
PM Mot Pole Count
Sets the number of PM motor poles.
Note:
When A1-02 = 7 [Control Method = PM CLVector], the maximum value is 120.
When A1-02 = 5, 6 or 8 [PM OLVector, PM AOLVector or EZ Vector], the
maximum value is 48.
Determined by E5-01
(2 - 120)
624
E5-05
(032D)
PM Mot Resistance
(Ohms/Phase)
Sets the resistance per phase of the PM motors. Set 50% of the line-to-line resistance.
Determined by E5-01
(0.000 - 65.000 Ω)
625
E5-06
(032E)
PM d-Axis Inductance
(mH/Phase)
Sets the PM motor d-axis inductance.
Determined by E5-01
(0.00 - 300.00 mH)
625
E5-07
(032F)
PM q-Axis Inductance
(mH/Phase)
Sets the PM motor q-axis inductance.
Determined by E5-01
(0.00 - 600.00 mH)
625
E5-09
(0331)
PM BackEMF Vpeak
(mV/(rad/ s))
Sets the peak value of PM motor induced voltage.
Determined by E5-01
(0.0 - 2000.0 mV/(rad/s))
625
E5-11
(0333)
Enc ZPulse Offset
Sets the encoder Z-pulse offset.
0.0 degrees
(-180.0 - +180.0
degrees)
625
E5-24
(0353)
PM BackEMF L-L Vrms
(mV/rpm)
Sets the RMS value for PM motor line voltage.
Determined by E5-01
(0.0 - 6500.0 mV/min
-1
)
626
E5-25
(035E)
Expert
Polar Est Timeout
Sets the function that switches polarity for initial polarity estimation. Usually it is not
necessary to change this setting.
0 : Disabled
1 : Enabled
0
(0, 1)
626
E9: SIMPLE VECTOR SETTINGS
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E9-01
(11E4)
Motor Type Selection
Sets the type of motor.
0 : IM (Induction)
1 : PM (Permanent Magnet)
2 : SynRM (Synchronous Reluctance)
0
(0 - 2)
626
E9-02
(11E5)
Maximum Speed
Sets the maximum speed of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
626
E9-03
(11E6)
Rated Speed
Sets the rated rotation speed of the motor.
Determined by E9-01
(100 - 7200 min
-1
)
627
E9-04
(11E7)
Base Frequency
Sets the rated frequency of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
627
E9-05
(11E8)
Base Voltage
Sets the rated voltage of the motor.
Determined by E9-01
(400 V Class: 0.0 to
510.0 V)
627
E9-06
(11E9)
Motor Rated Current
Sets the motor rated current in amps.
Determined by E9-01
and o2-04
(10% to 200% of the
drive rated current)
202
E9-07
(11EA)
Motor Rated Power
(kW)
Sets the motor rated power in 0.01 kW increments (1 HP = 0.746 kW).
Determined by E9-02
and o2-04
(0.00 - 650.00 kW)
627
E9-08
(11EB)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 120)
627
E9-09
(11EC)
Motor Rated Slip
Sets the motor rated slip.
0.0 Hz
(0.0 - 20.0 Hz)
628
E9-10
(11ED)
Motor L-L Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
628

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals