EasyManuals Logo

Omron Q2A Series Technical Manual

Omron Q2A Series
844 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #824 background imageLoading...
Page #824 background image
12.11 T: AUTOTUNING
824 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
12.11 T: AUTOTUNING
Numbers identifying the T parameters are displayed when an LED keypad is used. The names of the parameters
are displayed on the LCD screen of the LCD keypad. Set the following.
Induction Motor Auto-Tuning
PM Motor Auto-Tuning
ASR and Inertia Tuning
T0: TUNE MODE
T0-00 Tune Mode Selection
When your control method supports Control Tuning, set T0-00 first. Then, set T1-00 [Mot1/Mot2 Selection] to
select the motor you will tune. Then, set the tuning mode in T2-01 [PM AutoTune Mode Select] or T3-00 [Control
Loop Tune Selection].
No.
(Hex.)
Name Description
Default
(Range)
T0-00
(1197)
Tune Mode Selection
Sets the type of Auto-Tuning.
0
(0, 1)
0 : Motor Parameter Tuning
1 : Control Tuning
Note:
The available tuning modes are different for different control methods.
T1: INDUCTION MOTOR
T1 parameters set the Auto-Tuning input data for induction motor tuning.
Note:
The base frequency of drive dedicated motors and special motors for use with vector control may be lower than the base frequency of
general-purpose motors, which is 50 Hz or 60 Hz. In such cases, this lower frequency is used as the value for E1-06 [Base Frequency]
and E1-04 [Max Output Frequency] after Auto-Tuning completes. If the maximum output frequency is too low and causes problems,
change the setting of E1-04 after Auto-Tuning completes.
The following induction motor parameters are set automatically.
E1: V/F PARAMETER MOTOR 1
E2: MOTOR 1 PARAMETERS
E3: V/F PARAMETER MOTOR 2
E4: MOTOR 2 PARAMETERS
F1: ENCODER (only with Closed Loop Vector Control)
T1-00 Mot1/Mot2 Selection
No.
(Hex.)
Name Description
Default
(Range)
T1-00
(0700)
Mot1/Mot2 Selection
Sets which motor to tune when motor 1/2 switching is enabled. You can only use the keypad to set
this parameter. You cannot use external input terminals to set it.
1
(1, 2)
Note:
Set H1-xx = 16 [Motor 2 Selection] ON to set this parameter. The keypad will not show this parameter when H1-xx = 16 is OFF.
1 : Motor 1 (sets E1-xx, E2-xx)
Auto-Tuning automatically sets parameters E1-xx and E2-xx for motor 1.
2 : Motor 2 (sets E3-xx, E4-xx)
Auto-Tuning automatically sets parameters E3-xx and E4-xx for motor 2. Make sure that you connect motor 2 to
the drive for Auto-Tuning.

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals