4.6 Auto-Tuning
152 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Note:
Do not do Deceleration Rate Tuning if you use a braking resistor unit or a regenerative converter.
Do Deceleration Rate Tuning and KEB Tuning with the load attached to the motor.
Do not do Deceleration Rate Tuning or KEB Tuning for these applications:
In Deceleration Rate Tuning and KEB Tuning, the drive will automatically rotate the motor forward and accelerate and decelerate the
motor again and again.
On a machine that does not let the motor rotate forward
In applications with a small range of operation (trolleys and other such applications that can only move linearly)
In elevator applications
Applications where sudden acceleration and sudden deceleration are not applicable.
To do KEB Tuning with the external main circuit capacitors connected to the drive, set L3-26 [DC Bus Capacitors Extension] then do
KEB Tuning.
Do not do KEB Tuning or Deceleration Rate Tuning if the drive is set to use H1-xx = 61 [H1-xx: MFDI Function Select = Motor 2
Select]. Failure to obey can cause an ov [Overvoltage] fault.

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals