EasyManua.ls Logo

Omron Q2A Series - Page 173

Omron Q2A Series
844 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Standards Compliance
5
5.2 European Standards
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 173
Figure 5.2 Wiring Diagram for CE Low Voltage Directive Compliance
*1 Connect peripheral options to terminals -, +1, +2, B1, and B2.
WARNING! Electrical Shock Hazard. Use terminals -, +1, +2, B1, and B2 to connect options to the drive. Do not connect
an AC power supply lines to these terminals. Failure to obey can cause death or serious injury.
*2 For circuit protection, the main circuit is separated from the surface case that can touch the main circuit.
*3 The control circuit is a Safety Extra-Low Voltage circuit. Separate this circuit from other circuits with
reinforced insulation. Make sure that the Safety Extra-Low Voltage circuit is connected as specified.
*4 Reinforced insulation separates the output terminals from other circuits. Users can also connect circuits that
are not Safety Extra-Low Voltage circuits if the drive output is 250 Vac 1 A max. or 30 Vdc 1 A maximum.

Table of Contents

Other manuals for Omron Q2A Series

Related product manuals