EasyManuals Logo

Omron Q2A Series Technical Manual

Omron Q2A Series
844 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #205 background imageLoading...
Page #205 background image
Standards Compliance
5
5.3 UL Standards
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 205
When the motor operates at 150% load continuously for 1 minute after continuous operation at 100% load (hot
start), the default setting triggers the electronic thermal protector.
Figure 5.23 Example: Protection Operation Time for a General-purpose Motor at Rated Output Frequency
Motor overload protection operates in the range between a cold start and a hot start.
This example shows a general-purpose motor operating at the base frequency with L1-02 set to 1.0 min.
Cold start
Shows the motor protection operation time characteristics when the overload occurs immediately after starting
operation from a complete stop.
Hot start
Shows the motor protection operation time characteristics when overload occurs from continuous operation
below the motor rated current.
L1-03 Motor oH AL Reaction Select
No.
(Hex.)
Name Description
Default
(Range)
L1-03
(0482)
Motor oH AL Reaction
Select
Sets drive operation when the PTC input signal entered into the drive is at the oH3 [Motor
Overheat Alarm] detection level.
3
(0 - 3)
0 : Ramp->Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal 1NO-1CM turns ON and
1NC-1CM turns OFF.
1 : Coast->Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal 1NO-1CM turns ON, and 1NC-
1CM turns OFF.
2 : Fast Stop (C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal 1NO-
1CM turns ON, and 1NC-1CM turns OFF.
3 : Alarm Only
The keypad shows oH3, and operation continues. The output terminal set for Alarm [H2-01 to H2-03 = 4] turns
ON.
Motor oH FLT Reaction Select
No.
(Hex.)
Name Description
Default
(Range)
L1-04
(0483)
Motor oH FLT Reaction
Select
Sets the drive operation when the PTC input signal to the drive is at the oH4 [Motor Overheat
Fault (PTC Input)] detection level.
1
(0 - 2)
0 : Ramp->Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal 1NO-1CM turns ON and
1NC-1CM turns OFF.
1 : Coast->Stop

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals