6.2 Modbus Communications
246 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
No Response from Slave
The slave ignores the command message from the master and will not send a response message in these
conditions:
When a communications error (overrun, framing, parity, CRC-16) is detected in the command message.
When the slave address in the command message and the slave address for the drive side do not agree (Use H5-
01 [Mbus Address] to set the slave address of the drive)
When the time interval between the data of which the message is composed is longer than 24 bits
When the data length for the command message is not accurate
Note:
If the keypad shows CALL [Serial Comm Transmission Error], refer to Troubleshooting to remove the cause of the error, and try to
do communications again. If the keypad does not show CALL, check U1-19 [Modbus Err.Code] for the error and error type.
If you execute the write function code when the slave address in the command message is 00 (Hex.), all of the slaves will execute the
write command, but they will not send response messages to the master.

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals