EasyManuals Logo

Omron Q2A Series Technical Manual

Omron Q2A Series
844 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #429 background imageLoading...
Page #429 background image
Parameter List
11
11.7 F: OPTIONS
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 429
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-64
(0784)
PZD5 Write
Sets the Modbus address for PZD5 (PPO output). A value of 0, 1, or 2 will disable the
PZD5 (PPO output) write operation to the Modbus register.
0 663
F7-65
(0785)
PZD6 Write
Sets the Modbus address for PZD6 (PPO output). A value of 0, 1, or 2 will disable the
PZD6 (PPO output) write operation to the Modbus register.
0 663
F7-66
(0786)
PZD7 Write
Sets the Modbus address for PZD7 (PPO output). A value of 0, 1, or 2 will disable the
PZD7 (PPO output) write operation to the Modbus register.
0 663
F7-67
(0787)
PZD8 Write
Sets the Modbus address for PZD8 (PPO output). A value of 0, 1, or 2 will disable the
PZD8 (PPO output) write operation to the Modbus register.
0 663
F7-68
(0788)
PZD9 Write
Sets the Modbus address for PZD9 (PPO output). A value of 0, 1, or 2 will disable the
PZD9 (PPO output) write operation to the Modbus register.
0 663
F7-69
(0789)
PZD10 Write
Sets the Modbus address for PZD10 (PPO output). A value of 0, 1, or 2 will disable the
PZD10 (PPO output) write operation to the Modbus register.
0 663
F7-70
(078A)
PZD1 RD (StatWord)
Sets the Modbus address for PZD1 (PPO Read). PZD1 (PPO input) functions as the
ZSW when F7-70 = 0.
0 663
F7-71
(078B)
PZD2 RD (OutFreq)
Sets the Modbus address for PZD2 (PPO Read). PZD2 (PPO input) functions as the
HIW when F7-71 = 0.
0 664
F7-72
(078C)
PZD3 Read
Sets the Modbus address for PZD3 (PPO Read). A value of 0 will disable the PZD3
(PPO input) load operation from the Modbus register.
0 664
F7-73
(078D)
PZD4 Read
Sets the Modbus address for PZD4 (PPO Read). A value of 0 will disable the PZD4
(PPO input) load operation from the Modbus register.
0 664
F7-74
(078E)
PZD5 Read
Sets the Modbus address for PZD5 (PPO Read). A value of 0 will disable the PZD5
(PPO input) load operation from the Modbus register.
0 664
F7-75
(078F)
PZD6 Read
Sets the Modbus address for PZD6 (PPO Read). A value of 0 will disable the PZD6
(PPO input) load operation from the Modbus register.
0 664
F7-76
(0790)
PZD7 Read
Sets the Modbus address for PZD7 (PPO Read). A value of 0 will disable the PZD7
(PPO input) load operation from the Modbus register.
0 664
F7-77
(0791)
PZD8 Read
Sets the Modbus address for PZD8 (PPO Read). A value of 0 will disable the PZD8
(PPO input) load operation from the Modbus register.
0 664
F7-78
(0792)
PZD9 Read
Sets the Modbus address for PZD9 (PPO Read). A value of 0 will disable the PZD9
(PPO input) load operation from the Modbus register.
0 664
F7-79
(0793)
PZD10 Read
Sets the Modbus address for PZD10 (PPO Read). A value of 0 will disable the PZD10
(PPO input) load operation from the Modbus register.
0 665

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals