12.7 H: TERMINALS
680 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
ON : Deceleration during momentary power loss
OFF : Normal operation
When you enable KEB Ride-Thru 1, set L2-29 [KEB Method]. The drive operates with the selected KEB method.
Note:
If you set KEB Ride-Thru 1 [H1-xx = 40, 41] and KEB Ride-Thru 2 [H1-xx = 42, 43] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
Refer to "KEB Ride-Thru function" for more information.
42: KEB Thru2 NC
Setting Function Description
42 KEB Thru2 NC
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The L2-29
[KEB Method] setting will not have an effect.
Note:
If you set KEB Ride-Thru 1 [H1-xx = 40, 41] and KEB Ride-Thru 2 [H1-xx = 42, 43] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
Refer to KEB Ride-Thru function for more information.
43: KEB Thru2 NO
Setting Function Description
43 KEB Thru2 NO
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The L2-29
[KEB Method] setting will not have an effect.
Note:
If you set KEB Ride-Thru 1 [H1-xx = 40, 41] and KEB Ride-Thru 2 [H1-xx = 42, 43] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
Refer to KEB Ride-Thru function for more information.
44: Field weakening
Setting Function Description
44 Field weakening
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01[Field Weak
Level] and d6-02 [Field Weak FqLimit] when the input terminal is activated.
Note:
Refer to d6: FIELD WEAKENING / FORCING for more information.
45: ASR Gain Switch
Setting Function Description
45 ASR Gain Switch
Sets the function to switch the ASR proportional gain set in C5-01 [ASR PGain 1] and C5-03 [ASR PGain 2].
ON : C5-03
Switches the proportional gain to C5-03 [ASR PGain 2].
OFF : C5-01
Switches the proportional gain to C5-01 [ASR PGain 1].
Note:
Refer to C5: ASR - SPEED REGULATION for more information.

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals