EasyManuals Logo

Omron Q2A Series Technical Manual

Omron Q2A Series
844 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #705 background imageLoading...
Page #705 background image
Parameter Details
12
12.7 H: TERMINALS
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 705
19: @ShortCBraking
Setting Function Description
19 @ShortCBraking
The terminal activates during Short Circuit Braking.
Note:
When A1-02 = 8 [Control Method = EZ Vector], this function is available if you use a PM motor.
Refer to b2: DC INJ / SHORT CKT BRAKE for more information.
1A: @BaseblockNO
Setting Function Description
1A @BaseblockNO
The terminal turns on during baseblock. When the drive is in baseblock, the drive output transistor stops switching and the drive
will not make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
1B: @BaseblockNC
Setting Function Description
1B @BaseblockNC
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does
not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
1C: FreqRefSource
Setting Function Description
1C FreqRefSource
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Freq. Ref. Sel. 1 or Freq. Ref. Sel. 2] is the frequency reference source.
1D: RunCmdSource
Setting Function Description
1D RunCmdSource
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Comm. Sel 1 or Run Comm. Sel 2] is the Run command source.
1E: Motor2 Select
Setting Function Description
1E Motor2 Select
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
1F: Restart Enable
Setting Function Description
1F Restart Enable
The terminal activates when the Auto Restart function is trying to restart after a fault.
The terminal deactivates when the Auto Restart function automatically resets a fault. The terminal deactivates
when the Auto Restart function detects the fault again because the Auto Restart function cannot operate when the
drive reaches the number of attempts set with L5-01 [Auto-Reset Attempts].

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals