Parameter Details
12
12.10 o: KEYPAD
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 817
o4-11 Flt.History Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-11
(0510)
Flt.History Initialization
Resets the records of Monitors [U2: FAULT] and [U3: FAULT HISTORY].
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Init Parameters], the drive will not reset the records for U2-xx and U3-xx.
0 : No Reset
Keeps the records of Monitors U2-xx and U3-xx.
1 : Reset
Resets the records for Monitors U2-xx and U3-xx. After the reset, the drive automatically resets o4-11 to 0.
o4-12 kWh Monitor Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization
Resets the monitor values for U4-10 [kWh Lower 4Digits] and U4-11 [kWh Upper 5Digits].
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Initialize Parameters], the drive will not reset U4-10 and U4-11.
0 : No Reset
Keeps the monitor values for U4-10 and U4-11.
1 : Reset
Resets the values of U4-10 and U4-11. After the reset, the drive automatically resets o4-12 to 0.
o4-13 NumOfRunCom Init Counter
No.
(Hex.)
Name Description
Default
(Range)
o4-13
(0528)
NumOfRunCom Init
Counter
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [No of Travels(L)], and
U4-25 [No of Travels(H)].
0
(0, 1)
0 : No Reset
Keeps the monitor values for U4-02, U4-24, and U4-25.
1 : No Reset
Resets the values of U4-02, U4-24, and U4-25. After the reset, the drive automatically resets o4-13 to 0.
o4-22 Time Format
No.
(Hex.)
Name Description
Default
(Range)
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD keypad.
0
(0 - 2)
Sets the display of the time shown in the upper-left of the LCD keypad screen.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
o4-23 Date Format
No.
(Hex.)
Name Description
Default
(Range)
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when using an LED keypad.
0
(0 - 2)
Sets the date format that the drive uses for the fault history and other records.

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals