11
Wire Sizes and Types
200-V-class 3-phase Input Series:
Circuit Model
Inverter
Terminal symbol Terminal
Wire size
Wire type
3G3XV capacity
screw
AWG mm
2
Main
circuit
A2001
0.3 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
Power cable:
600 V
G (E) 14-10 2 to 5.5
vinyl-sheathed
A2002
0.6 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
lead or
equivalent
G (E) 14-10 2 to 5.5
A2004
1.1 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
A2007
1.9 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
A2015
2.5 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 12-10 3.5 to 5.5
G (E) 14-10 2 to 5.5
A2022
4.2 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 12-10 3.5 to 5.5
G (E) 14-10 2 to 5.5
A2037
6.7 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 12-10 3.5 to 5.5
G (E) 14-10 2 to 5.5
Control
circuit
Common
to all
––– 1 to 14,
FLT-A, FLT-B, FLT-C
M3.5
20-14 0.5 to 2 Shielded lead
or equivalent
Models
G (E)
200-V-class Single-phase Input Series:
Circuit Model
Inverter
Terminal symbol Terminal
Wire size
Wire type
3G3XV capacity
screw
AWG mm
2
Main
circuit
AB001
0.3 kVA L1 (R), L2 (S), B1/⊕, B2, T1
(U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
Power cable:
600 V
G (E) 14-10 2 to 5.5
vinyl-sheathed
AB002
0.6 kVA L1 (R), L2 (S), B1/⊕, B2, T1
(U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
lead or
equivalent
G (E) 14-10 2 to 5.5
AB004
1.1 kVA L1 (R), L2 (S), B1/⊕, B2, T1
(U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
AB007
1.9 kVA L1 (R), L2 (S), B1/⊕, B2, T1
(U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
Wiring Section 1-4