12
Circuit Wire typeWire sizeTerminal
screw
Terminal symbolInverter
capacity
Model
3G3XV
Circuit Wire type
mm
2
AWG
Terminal
screw
Terminal symbolInverter
capacity
Model
3G3XV
Main
circuit
AB015
2.5 kVA L1 (R), L2 (S), B1/⊕, B2, T1
(U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
Power cable:
600 V
G (E) 14-10 2 to 5.5
vinyl-sheathed
AB022
4.2 kVA L1 (R), L2 (S), B1/⊕, B2, T1
(U), T2 (V), T3 (W)
M5 12-8 3.5 to 8
lead or
equivalent
G (E) 14-8 2 to 8
AB037
6.7 kVA L1 (R), L2 (S), B1/⊕, B2, T1
(U), T2 (V), T3 (W)
M5 10-8 5.5 to 8
G (E) 14-8 2 to 8
Control
circuit
Common
to all
––– 1 to 14,
FLT-A, FLT-B, FLT-C
M3.5
20-14 0.5 to 2 Shielded lead
or equivalent
Models
G (E)
400-V-class 3-phase Input Series:
Circuit Model
Inverter
Terminal symbol Terminal
Wire size
Wire type
3G3XV capacity
screw
AWG mm
2
Main
circuit
A4002
0.8 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
Power cable:
600 V
G (E) 14-10 2 to 5.5
vinyl-sheathed
A4004
1.2 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
lead or
equivalent
G (E) 14-10 2 to 5.5
A4007
2.0 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
A4015
3.0 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
A4022
3.7 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
A4037
6.1 kVA L1 (R), L2 (S), L3 (T), B1/⊕,
B2, T1 (U), T2 (V), T3 (W)
M4 14-10 2 to 5.5
G (E) 14-10 2 to 5.5
Control
circuit
Common
to all
––– 1 to 14,
FLT-A, FLT-B, FLT-C
M3.5
20-14 0.5 to 2 Shielded lead
or equivalent
Models
G (E)
Wiring Section 1-4