43
Function See
Page
User
set
values
Initial
setting
DescriptionNameNo.
Function setting 46 Operation
selection
after
momentary
power loss
1
st
digit = 0: Operation stopped by
momentary power loss
detection
= 1: Operation continues after
momentary power loss
0110 59
Enable/Dis-
able setting
constants 9
to 17, 22,
23, 29, 45,
and 57 in
DRIVE
mode
2
nd
digit = 0: Read only
= 1: Write possible
60
Selection
level of stall-
preventive
operation
during
acceleration
3
rd
digit = 0: Level of stall-preventive
operation during accelera-
tion is constant in the
motor constant output
power area
= 1: Level of stall-preventive
operation during accelera-
tion is automatically
decreased in the motor
constant output power
area.
Note Motor constant output power area is
a frequency area higher than the
maximum voltage frequency (base
frequency). Set the 3rd digit to “1”
when using a high-speed motor.
Auto reset/re-
start operation
47 No. of auto
restart
attempts
Setting unit: 1 time
Setting range: 0 to 10 times
(Setting to 0 disables fault retry function.)
0 60
Fault trace 48 Fault record The latest fault is number of auto restart
attempt: 0 to 10 (setting disabled).
---
Software ver-
sion
49 PROM No. PROM No. (04100) is displayed (setting
disabled).
---
Frequency
jump control
50 Setting pro-
hibit fre-
quency 1
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0
0.0 Hz 60
51 Setting pro-
hibit fre-
quency 2
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0
0.0 Hz
52 Setting pro-
hibit fre-
quency 3
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0
0.0 Hz
53 Setting pro-
hibit fre-
quency
range
Setting unit: 0.1 Hz, setting range: 0.0 to
25.5
1.0 Hz