3
Interval Timer CPM1 PCs have a high-speed interval timer which can be set from 0.5 ms to
319968 ms. The timer can be set to trigger a single interrupt (one-shot mode) or
repeat scheduled interrupts (scheduled interrupt mode).
High-speed Counter CPM1 PCs have a high-speed counter that can be used in incremental mode or
up/down mode. The high-speed counter can be combined with input interrupts
to perform target value control or zone comparison control that isn’t affected by
the PC’s cycle time.
Analog Setting Function The CPM1 PCs have 2 analog volume controls that can be used to make manual
analog settings.
Host Link Communications The CPM1 PCs are compatible with the Host Link, which allows communica-
tions with personal computers. The CPM1 using the Host Link can also commu-
nicate with Programmable Terminal using host link commands.
An RS-232C Adapter is used for 1-to-1 communications and an RS-422 Adapter
is used for 1-to-n communications.
1-to-1 Link A data link can be created with a data area in another CPM1, CQM1, or C200HS
PC. An RS-232C Adapter is used to make the 1-to-1 connection.
NT Link Communications High-speed operations can be achieved by providing a direct access by con-
necting the CPM1 to the Programmable Terminal through the NT Link Interface.
An RS-232 Adapter is used for this connection.
Standard Peripheral Devices The CPM1 uses the same Programming Consoles, SYSMAC Support Software
(SSS), and Ladder Support Software (LSS) as the Mini H-type and CQM1 PCs.
Programming operation is possible through the PT screen by using an OMRON
PT that has a built-in Programming Console function.
1-1-2 I/O Terminal – IR Bit Allocation
The following table shows which IR bits are allocated to the I/O terminals on the
CPM1’s CPU Unit and Expansion I/O Unit.
Note Refer to Section 6 Analog I/O Unit for details on I/O allocation for the Analog I/O
Unit.
Number of
I/O terminals
CPU Unit terminals Expansion I/O Unit terminals
Power
supply
Model number
I/O terminals
on the CPU
Unit
Inputs Outputs Inputs Outputs
supply
10 6 points: 4 points: 12 points: 8 points:
AC CPM1-10CDR-A
00000 to 00005 01000 to 01003 00100 to 00111 01100 to 01107
DC CPM1-10CDR-D
20 12 points: 8 points: 12 points: 8 points:
AC CPM1-20CDR-A
00000 to 00011 01000 to 01007 00100 to 00111 01100 to 01107
DC CPM1-20CDR-D
30 18 points: 12 points: 12 points: 8 points:
AC CPM1-30CDR-A
00000 to 00011 01000 to 01007 00200 to 00211 01200 to 01207
DC CPM1-30CDR-D
00100 to 00105 01100 to 01103
36 points:
00200 to 00211
24 points:
01200 to 01207
AC CPM1-30CDR-A-V1
00300 to 00311
00400 to 00411
01300 to 01307
01400 to 01407
DC CPM1-30CDR-D-V1
Programming is Possible
Using the PT
CPM1 Features and Functions Section 1-1