5-46
5
Digital Operator: o2
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Closed
Loop
Vector
(PM)
Display
o2-01
LOCAL/
REMOTE key
enable/disable
Enables/Disables the Digital
Operator Local/Remote key
0:Disabled
1:Enabled (Switches between
the Digital Operator and the
parameter settings
b1-01, b1-02.)
0 or 1 0 No A A A A 505H 6-65
Local/Remote
Key
o2-02
STOP key during
control circuit ter-
minal operation
Enables/Disables the Stop key in
the run mode.
0:Disabled (When the run com-
mand is issued from an exter-
nal terminal, the Stop key is
disabled.)
1:Enabled (Effective even dur-
ing run.)
0 or 1 0 No A A A A 506H 6-65
Oper Stop Key
o2-03
User parameter
initial value
Clears or stores user initial val-
ues.
0:Stores/not set
1:Begins storing (Records the
set parameters as user initial
values.)
2:All clear (Clears all recorded
user initial values)
When the set parameters are
recorded as user initial values,
1110 will be set in A1-03.
0 to 2 0 No A A A A 507H 6-65
User Defaults
o2-04
kVA selection
Do not set unless after replacing
the control board. (Refer to page
5-61 for the setting values).
0 to FF 0 No A A A A 508H 6-65
Inverter Model #
o2-05
Frequency refer-
ence setting
method selection
Sets whether the ENTER key is
needed for a frequency refer-
ence change or not when the
Digital Operator is selected as
frequency reference source.
0:Enter key needed
1:Enter key not needed
If “1” is selected, a frequency
reference change is accepted
without the need of pressing the
Enter key.
0 or 1 0 No A A A A 509H 6-66
Operator M.O.P.
o2-06
Operation selec-
tion when digital
operator is dis-
connected
Sets the operation when the Dig-
ital Operator/LED Monitor is
disconnected.
0:Operation continues even if
the Digital Operator/LED
Monitor is disconnected.
1:OPR is detected at Digital
Operator/LED Monitor dis-
connection. Inverter output is
switched off, and the fault con-
tact is operated.
0 or 1 0 No A A A A 50AH 6-66
Oper
Detection
o2-07
Cumulative oper-
ation time setting
Sets the cumulative operation
time in hour units.
0 to
65535
0 hr. No A A A A 50BH 6-66
Elapsed Time Set
o2-08
Cumulative oper-
ation time selec-
tion
0:Accumulated inverter power
on time.
1:Accumulated inverter run
time.
0 or 1 1 No A A A A 50CH 6-66
Elapsed Time
Run