Setting Example
When the timer function input is ON for longer than b4-01, the timer output function is turned ON. When the
timer function input is OFF for longer than b4-02, the timer output function is turned OFF. An example of
timer function operation is given in the following diagram.
Fig 6.21 Timer Function Operation Example
Motor Contactor Answer Back Detection
The motor contactors can be observed using the motor contactor answer back function. Therefore an auxiliary
contact of the motor contactors must be connected to a digital input which is set to for this function
(H1-=86). If the contactor close command is set and no answer back signal comes from the contactor, the
inverter detects a SE1 fault (see below). Parameter S1-28 selects if the detection is enabled or disabled and
whether the SE1 fault is reset automatically or if has to be reset manually.
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Parameter
No.
Name
Factory
Setting
Change
during
Operation
Control Methods
V/f
Open
Loop
Ve ct or
Closed
Loop
Vector
Closed
Loop
Vector
(PM)
S1-28
Selects how a SE1 fault is reset.
0: Manual Reset
1: Automatic reset at stop
2: No SE1 detection
0 No AAAA
Set
Val ue
Function
Control Methods
V/f
Open
Loop
Ve ct or
Closed
Loop ´
Ve ct or
Closed
Loop
Vector
(PM)
86 Motor contactor answer back Yes Yes Yes Yes
Timer function input
Timer function output