7-13
7
OPE10
V/f Ptrn Setting
V/f Parameter Setting Error
V/f parameter settings were out of
range.
Check parameters (E1-). A fre-
quency/voltage value may be set
higher than the maximum fre-
quency/voltage.
ERR
EEPROM R/W Err
EEPROM write error
The NV-RAM data does not match the
EEPROM data.
A verification error occurred when
writing EEPROM.
Cycle power to the Inverter.
Do a factory initialization (A1-03)
Table 7.4 Operator Programming Errors
Display Meaning Probable Causes Corrective Actions