9.15.4 Totalizer 1 reset (Reset Total 1)
The transmitter is provided with counters (Counters 1 and 2) and totalizers (Totalizers 1 and 2) which
work in synchronism with pulse output. When an input arrives across status input terminals, counter 1
and totalizer 1 are reset to 0.
In this connection, counter 1 and totalizer 1 respond to pulse 1 output while counter 2 and totalizer 2
respond to pulse 2. (For detail of the function, see 9.10 Reset Functions.)
(1) Operating procedure
Select "Reset D/T 1" in selecting the status input function assignment.
(See 9.2.5 Transition chart (4) [No. 2 to 5-1].)
Set the input mode of status input. According to the settings, the following input mode will be
enabled:
"Short Active" setting: the function is activated 0.3 seconds after the condition of the circuit
between status input terminals is changed from opened to shorted.
"Open Active" setting: the function is activated 0.3 seconds after the condition of the circuit
between status input terminals is changed from shorted to opened.
(See 9.2.5 Transition chart (4) [No.2 to 5-2])
The function becomes available by setting the above.
9.15.5 Totalizer 2 reset (Reset Total 2)
The transmitter is provided with counters (Counters 1 and 2) and totalizers (Totalizers 1 and 2) which
work in synchronism with pulse output. When an input arrives across status input terminals, counter 2
and totalizer 2 are reset to 0.
In this connection, counter 1 and totalizer 1 respond to pulse 1 output while counter 2 and totalizer 2
respond to pulse 2. (For detail of the function, see 9.10 Reset Function.)
(1) Operating procedure
Select "Reset C/T 2" in selecting the status input function assignment.
(See 9.2.5 Transition chart (4) [No. 2 to 5-1].)
Set the input mode of status input. According to the settings, the following input mode will be
enabled:
"Short Active" setting: the function is activated 0.3 seconds after the condition of the circuit
between status input terminals is changed from opened to shorted.
"Open Active" setting: the function is activated 0.3 seconds after the condition of the circuit
between status input terminals is changed from shorted to opened.
(See 9.2.5 Transition chart (4) [No.2 to 5-2])
The function becomes available by setting the above.