2-4
2.2 Power Supply Specifications
2.2.1 AC Power Supply
Item Specifications
Rated voltage 100 to 240 V AC
Voltage regulation range 85 to 264 V AC
Inrush current
L14: 35A or less (at 240 V AC, 25 C)
L30/L40/L60: 40A or less (at 240 V AC, 25 C)
Momentary power off time 10 ms (when using 100 V AC)
Frequency 50/60 Hz (47 to 63 Hz)
Leakage current 0.75 mA or less between input and protective earth terminals
Internal power supply part
Guaranteed life
20,000 hours (at 55 C)
Fuse Built-in (Cannot be replaced)
Insulation system Transformer insulation
Terminal screw M3
2.2.2 Service Power supply for Input (Output) (L30, L40 and L60 only)
Item Specifications
Rated output voltage 24 V DC
Voltage regulation range 21.6 to 26.4 V DC
Rated output current 0.4 A
Overcurrent protection
function
Note)
Available
Terminal screw M3
Note) This is a function to protect overcurrent temporarily, which protects the output short-circuit. If the
short-circuit is detected, all the power supply for the PLC will be turned off. If a current load that is
out of the specifications is connected and the overloaded status continues, it may lead to damages.