3.2 FP-X Expansion FP0 Adapter
3.2.1 Parts Names, Functions and Specifications
FP-X expansion FP0 adapter (AFPX-EFP0)
○
1
When the power of 24 V DC is supplied and the communication starts with the
control unit, the LED lights. When the communication cannot be carried out, it
When the communication starts with the control unit, the LED lights. When the
communication cannot be carried out, it goes out.
When the FP0 expansion unit is not connected, it flashes.
When an error occurs on the connection with the FP0 expansion unit, it flashes.
○
2
FP-X expansion bus connector
Connects the FP-X control unit (or FP-X expansion unit). The provided expansion cable (AFPX-EC08) is
used for the connection.
It is not necessary to specify the TERM (terminal) setting for the expansion FP0 adapter.
○
3
Power supply connector (24V DC)
Supply the power of 24 V DC. The provided power supply cable (AFP0581) is used for the connection.
Supply the power from the service power supply for the input of the FP-X control unit.
○
4
FP0 expansion connector
Connects the FP0 expansion unit.
○
5
Expansion hook
This hook is used to secure the FP0 expansion unit.
○
6
DIN rail attachment lever
This lever enables the expansion unit to attach toa DIN rail at a touch. The lever is also used for
installation on the mounting plate slim type) (AFP0803).
General specifications
20A or less (24 V DC, at 25 °C)
Built-in (Replacement is not available)
3-pin connector (Power supply cable AFP0581 is provided.)