228
15.7.3 95 x 95 Cassette (UA1E5 Series)
Air swing direction setting Manual
Mode Condition
Step 1 Step 2 Step 3 Step 4
Normal 20° 35° 50° 70°
Deice 10°
Hot start 10°
Heat removal control 20°
Heat
Thermostat OFF 20°
Normal 20° 35° 50° 70°
Dew control 35°
Cool/Fan
Thermostat OFF 20° 35° 50° 70°
Normal 35°
Dew control 35°
Dry
Thermostat OFF 20° 35° 50° 70°
Automatic mode judgment 20° 35° 50° 70°
Operation stop 0°
Air swing direction setting Automatic
Mode Condition
Zone A 70° 70° 70°
Zone B 20° ~ 70° 20° ~ 50° 40° ~ 70°
Indoor heat
exchanger
temperature
Zone C 20° 20° 20°
Deice 10°
Hot start 10°
Heat removal control 20°
Heat
Thermostat OFF 20°
Normal 20° ~ 70° 20° ~ 50° 40° ~ 70°
Dew control 35°
Cool/Fan
Thermostat OFF 20° ~ 70° 20° ~ 50° 40° ~ 70°
Normal 30°
Dew control 35°
Dry
Thermostat OFF 20° ~ 70° 20° ~ 50° 40° ~ 70°
Automatic mode judgment 20° 20° 20°
Operation stop 0°
• Heating automatic air swing control according indoor unit heat exchanger temperature.
60
o
C
57
o
C
Zone A
Zone B
Zone C
25
o
C
30
o
C
Indoor heat exchanger temperature