6-3 Programming Your Application
650 Series AC Drive
MMI Parameters Table
Display Parameter Description Range Default
FIXED BOOST
M VF
Used to correctly flux the motor at low speeds. This
allows the drive to produce greater starting torque
for high friction loads. It increases the motor volts
above the selected V/F characteristic at the lower
end of the speed range
OUTPUT VOLTS
FREQUENCY
f
B
25%
100%
BOOST
f
B
= BASE FREQUENCY
0%
INCREASING
INCREASED
TORQUE
CONSTANT
POWER RANGE
FLUXING
NORMAL FLUXING
0.00 to 25.00% product
code
dependent
PASSWORD A password may be set to prohibit unauthorised
adjustment of parameters. When
P
99 is set to
non-zero you will be required to match this value
before parameters can be adjusted
0000 – FFFF 0000
Parameters
P
301 to
P
308 are visible in the PAR menu when Application 3 is selected in parameter
P
1
PRESET 0 A user-adjustable speed preset, set by
potentiometer
-100.00 to 100.00 -
PRESET 1 A user-adjustable speed preset -100.00 to 100.00 20.00
PRESET 2 A user-adjustable speed preset -100.00 to 100.00 50.00
PRESET 3 A user-adjustable speed preset -100.00 to 100.00 100.00
PRESET 4 A user-adjustable speed preset -100.00 to 100.00 -10.00
PRESET 5 A user-adjustable speed preset -100.00 to 100.00 -20.00
PRESET 6 A user-adjustable speed preset -100.00 to 100.00 -50.00
PRESET 7 A user-adjustable speed preset -100.00 to 100.00 -100.00
Parameters
P
401 to
P
404 are visible in the PAR menu when Application 4 is selected in parameter
P
1
R/L RAMP TIME The time taken to ramp the Raise/Lower output
from 0.00% to 100.00% of its value
0.0 to 600.0s 10.0s
R/L MAX VALUE The maximum value for the ramp output -100.00 to 100.00% 100.00%
R/L MIN VALUE The minimum value for the ramp output -100.00 to 100.00% 0.00%
R/L RESET VALUE The value the output is set to when Reset is TRUE,
when DIN4 (terminal 10) is 24V in Application 4
-100.00 to 100.00% 0.00%
Parameters
P
501 and
P
506 are visible in the PAR menu when Application 5 is selected in parameter
P
1
PI P GAIN The PI proportional gain 0.00 to 100.00 0.10
PI I GAIN The PI integral gain 0.00 to 100.00 1.00
PID D GAIN
F
The PID derivative gain 0.00 to 100.00 0.00
PID D FILTER TC
F
In order to help attenuate high frequency noise on
the derivative term, a first order lag has been
provided. This parameter determines the filter time
constant.
0.05 to 10.00s 0.05s
PID FEEDBACK
GAIN
F
A multiplier applied to the feedback signal of the
PID
-10.00 to 10.00 1.00
PID LIMIT
F
Determines the maximum positive and negative
excursion (Limit) of the PID output
0.00 to 300.00% 300.00%
PID SCALING
F
This parameter represents an overall scaling factor
which is applied after the PID positive and negative
limit clamps
-3.0000 to 3.0000 1.0000