Programming Your Application 6-4
650 Series AC Drive
MMI Parameters Table
Display Parameter Description Range Default
PID ERROR
F
The result of SETPOINT - FEEDBACK x FEEDBACK
GAIN
—.xx % —.xx%
PID OUTPUT
F
The output of the PID function block
—.xx % —.xx %
SET::IN Menu
DIN 1 INVERT Inverts the value of the signal, TRUE or FALSE. 0= FALSE
1= TRUE
0
DIN 2 INVERT As
S
IP01 As
S
IP01 0
DIN 3 INVERT As
S
IP01 As
S
IP01 0
DIN 4 INVERT As
S
IP01 As
S
IP01 0
AIN 1 SCALE -300.0 to 300.0% 100.0%
AIN 1 OFFSET -300.0 to 300.0% 0.0%
AIN 1 TYPE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
0= 0-10V
1= 0-5V
0
AIN 2 SCALE -300.0 to 300.0% 100.0%
AIN 2 OFFSET -300.0 to 300.0% 0.0%
AIN 2 TYPE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
0= 0-10V
1= 0-5V
2= 0-20mA
3= 4-20mA
3
DIN 1 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
-
DIN 2 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
-
DIN 3 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
-
DIN 4 VALUE
F
The TRUE or FALSE input (after any inversion) 0=FALSE
1=TRUE
-
AIN 1 VALUE
F
The input reading with scaling and offset applied
⎯.x%
—.x%
AIN 2 VALUE
F
The input reading with scaling and offset applied
⎯.x%
—.x%
SET::OUT Menu
AOUT 1 SOURCE
ANALOG OUTPUT
0 NONE
1 DEMAND %
2 CURRENT %
3 PI ERROR %
4 RAISE/LOWER %
SCALE
OFFSET
ABSOLUTE
0-10V
OUTPUT
0= NONE
1= DEMAND
2= CURRENT
3= PID ERROR
4= RAISE/LOWER
OUTPUT
1
AOUT 1 SCALE -300.00 to 300.00% 100.00%
AOUT 1 OFFSET -300.00 to 300.00% 0.00%
AOUT 1
ABSOLUTE
0= FALSE
(not absolute)
1= TRUE (absolute)
1
AOUT 1 VALUE
F
+
SCALE
OFFSET
X
VALUE
ABS
X
OUTPUT
100%
0%
CLAMP
-300.0 to 300.0% 0.0%