6-5 Programming Your Application
650 Series AC Drive
MMI Parameters Table
Display Parameter Description Range Default
DOUT 2 SOURCE
Refer to
Configuring
Terminal 10
(Digital
Input/Output)
,
page 6-8.
DIN4 / DOUT2
0 NONE
1 HEALTH
2 TRIPPED
3 RUNNING
4 AT ZERO
5 AT SPEED
INVERT (output)
0= NONE
1= HEALTH
2= TRIPPED
3= RUNNING
4= AT ZERO
5= AT SPEED
0
DOUT 2 INVERT (OUTPUT) As
S
IP01. Set to 0 for applications 1 & 5. As
S
IP01 0
DOUT 2 VALUE
F
The TRUE or FALSE output demand. 0=FALSE
1=TRUE
0
RELAY SOURCE NONE : Relay is open
Relay is closed when:
HEALTH : the Run signal is not present, or no trip
is active
TRIPPED : a trip is present
RUNNING : the motor is running
AT ZERO : the output frequency is below 1% of
MAX SPEED (
P
2)
AT SPEED : the output frequency is at or near
Setpoint and within ±1% of MAX SPEED, set by
(
P
2). For example: if MAX SPEED = 50Hz and
Setpoint = 30Hz, then 1% of MAX SPEED = 0.5Hz.
So AT LOAD is True between 30 ±0.5Hz.
RELAY
0 NONE
1 HEALTH
2 TRIPPED
3 RUNNING
4 AT ZERO
5 AT SPEED
INVERT (output)
As
S
OP21 1
RELAY INVERT Inverts the value of the signal, TRUE or FALSE. 0=FALSE
1=TRUE
0
RELAY VALUE
F
The TRUE or FALSE output demand.
0=FALSE
1=TRUE
0
SET::TRIP Menu
DISABLE LOOP Disables LOST I LOOP trip (4-20mA) 0= TRIP ENABLED
1= TRIP DISABLED
1
AIN2 OVERLOAD Disables the overload trip (Terminal 3) As
S
LOOP 0
DISABLE STALL Disables STALL trip As
S
LOOP 0
DISABLE MOTOR
OVERTEMP
Disables the motor thermistor trip As
S
LOOP 0
INVERSE TIME Disables the inverse time trip As
S
LOOP 1
DISPLAY
(KEYPAD)
Disables the display (keypad) trip As
S
LOOP 0
DC LINK RIPPLE
F
Disables the DC link ripple trip As
S
LOOP 0