12-3 Applications
650 Series AC Drive
Application 1: Basic Speed Control (default)
This Application is ideal for general purpose applications. It provides push-button or switched start/stop control. The
setpoint is the sum of the two analogue inputs AIN1 and AIN2, providing Speed Setpoint + Speed Trim capability.
10k Speed
Setpoint
User Relay
10
9
8
7
6
5
4
3
2
1
RL1A
RL1B
WIRE
SINGLE
STARTING
DIN4/DOUT2 NOT STOP
24V = RUN FWD & RUN REV signals latched,
DIN3 JOG 24V = jog
DIN2 DIRECTION 0V = remote forward, 24V = remote reverse
DIN1 RUN FORWARD 24V = run forward
+24V
AOUT RAMP OUTPUT
DEMAND (0V = 0%, 10V = 100%)
+10V REF
AIN2 SPEED TRIM
4mA = 0%, 20mA = 100%
AIN1 SPEED SETPOINT
0V = 0%, 10V = 100%
0V
DOUT3 RELAY SOURCE
HEALTH i.e. 0V = not healthy
24V
+10V REF
0V
Control
Terminal
0V = RUN FWD & RUN REV signals not latched
= 0
= 3
= 1
= 1
default source
A or V
= 4-20mA
Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN +46 (0)18-65 70 00 +46 (0)18-10 74 78 info@regal.se www.regal.se