EasyManuals Logo

Parker AC10 series User Manual

Parker AC10 series
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
13-7 The Default Applications
AC10 Inverter
This is ideal for applications requiring multiple discrete speed levels.
The set-point is selected from either the sum of the analogue inputs, or as one of up to eight
other pre-defined speed levels. These are selected using DI2, DI3 and DI4, refer to the Truth
Table below.
Preset Speed Truth Table
DI4
DI3
DI2
Preset
Application 3: Preset Speeds
Parameters Setting:
F223 = 3
F106 = 2
F203 = 4
F204 = 1
F207 = 1
F316 = 56
F317 = 3
F318 = 4
F319 = 5
F320 = 8
F431 = 0
0V
0V
0V
1
0V
0V
24V
2
0V
24V
0V
3
0V
24V
24V
4
24V
0V
0V
5
24V
0V
24V
6
24V
24V
0V
7
24V
24V
24V
8
Coast stop
1
2
3
5
6
4
7
8
9
10
11
12
13
14
15
16
17
18
TA
TB
TC
1DO
24V
CM
DI1
DI2
DI3
DI4
DI5
10V
1AI
2AI
GND
1AO
A+
B-
REF
Run forward
Speed trim
not used
not used
Analog output
F 431=0 , running
frequency is output.
GND
Speed trim AI2 input 4-20 mA
Speed setpoint AI 1 input 0-10V
10V
Coast stop
Preset select 1
Auto run
CM
24V
not used
Relay output
See truth table below
F 300=1 , inverter outputs
fault signal.
See truth table below
Preset select 2
Preset select 3
See truth table below
Preset select 1
Preset select 2
Preset select
3
TC-Hydraulik - Rsdorfer Str. 8 - 25746 Heide - Lars Lornsen - T: +49 481 909 - 34 - l.lornsen@tc-hydraulik.de - www.tc-hydraulik.de

Table of Contents

Other manuals for Parker AC10 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC10 series and is the answer not in the manual?

Parker AC10 series Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
Analog Inputs2
Analog Outputs1
Communication OptionsModbus RTU
Protection RatingIP20
Input Voltage200-240VAC, 380-480VAC, 500-575VAC, 600VAC, 690VAC
Digital Outputs2
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Humidity5% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
BrakingBuilt-in dynamic braking

Related product manuals