14-6 Compliance
AC10 Inverter
14.3.4 Terminal Wiring Information
Frame Size Terminal Type
Required
Torque (in-lbs)
Wire Range
(AWG)
Wire Type
16G-31-0025-XX
16G-31-0045-XX
Input and Output
Terminal Block
10 12 STR/SOL
16G-31-0070-XX
16G-31-0100-XX
Input and Output
Terminal Block
10 10 STR/SOL
16G-11-0025-XX
16G-11-0045-XX
Input and Output
Terminal Block
10 14 STR/SOL
16G-11-0070-XX
16G-11-0100-XX
Input and Output
Terminal Block
10 14 STR/SOL
16G-41-0020-XX
16G-41-0040-XX
16G-41-0065-XX
Input and Output
Terminal Block
10 14 STR/SOL
16G-41-0080-XX
16G-41-0090-XX
Input and Output
Terminal Block
10.5 14 STR/SOL
16G-42-0120-XX
Input and Output
Terminal Block
10.5 10 STR/SOL
16G-42-0170-XX
Input and Output
Terminal Block
19 10 STR/SOL
16G-43-0230-XX
Input and Output
Terminal Block
30.4 8 STR/SOL
16G-43-0320-XX
Input and Output
Terminal Block
30.4 6 STR/SOL
Grounding The pressure wire connector intended for connection for field installed equipment,
grounding conductor shall be plainly identified such as being marked “G”, “GRD”, “Ground”,
“Grounding”, or equivalent or with the grounding symbol (IEC 417, Symbol 5019).