1
2
3
010 0.5
020 0.8
030 1.3
040 1.8
050 2.5
BIFFI ICON 2000
InstructIon and operatIng manual
Please make sure that:
- The joint surfaces are greased with silicone
oil or equivalent before assembly.
- The cable glands have minimum protection
degree IP6X (EN 60529).
- Periodically verify the quantity of dust
deposited on the enclosure and clean it if
more than 5 mm.
3.10 INSTALLATION IN ENVIRONMENT WITH
EXPLOSIVE DUSTS
IMPORTANT
Electric actuator ICON 2000 shall be installed
and maintained; according to the applicable rules
regarding the electrical installations in hazardous
area (other than mines) classified as zone 21
(dust); example: EN 50281-1-2 (dust) and/or other
national standards.
4. LUBRICATION
4.1 LUBRICATION INSPECTION
The actuator is lubricated for life, therefore
under normal working conditions it is not
necessary to replace or refill the oil. However it
is recommended to check the oil level every 3-5
years using holes 1 or 2 depending on mounting
position.
The actuator is fitted with oil plugs (parts 1, 2),
so that any assembly on the valve has at least
one oil plug on the upper part of the housing
and one on the lower part.
A spherical head lubricator (part 3) is fitted on
the coupling block for the proper greasing of
the inside thrust or sliding bearings.
The actuator is supplied with oil and greased
where necessary.
Actuator size
(DN)
Oil quantity
(l)
In case of maintenance the following OILS are
recommended:
Ambient temperature from -30°C to +85°C
(-20°C to 65°C for Ex d e version only)
•SHELL-TIVELAOILSC320
Other equivalent:
•EXXONTERESSTICSHP320
•MOBILOIL-GLYGOYLEHE320
•KLUBERLUBRICATION-KLUBERSYNTH
EG4-320
Ambient temperature from -55°C to +65°C
•SHELL-CASSIDA FLUIDHF68
Other equivalent:
•SYNECO-WINTERPLUS
In case of maintenance the following GREASES
are recommended:
Ambient temperature from -30°C to +85°C
(-20°C to 65°C for Ex d e version only)
•ISOviscositygradeX1(EP1)
Other equivalent:
•ESSOBEACONEP1
•AGIPGRMU/EP1
Ambient temperature from -55°C to +65°C
•FUCHSFN20
Other equivalent:
•TEXACOlowtemperaturegreaseEP
•AGIPFN20/00

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pentair Biffi ICON 2000 and is the answer not in the manual?

Pentair Biffi ICON 2000 Specifications

General IconGeneral
BrandPentair
ModelBiffi ICON 2000
CategoryController
LanguageEnglish

Related product manuals