19
4
6
1
3
2
5
BIFFI ICON 2000
InstructIon and operatIng manual
6. LOCAL CONTROLS
6.1 DESCRIPTION OF THE LOCAL OPERATOR
INTERFACE
The following functions are available by the
ICON 2000 local operator interface: Numeric display to indicate the present valve
positionasa%oftheopening.
Display resolution in function of the actuator
stroke turns:
-From2.8to5.5turns=1%
-From5.5to13.8turns=0.5%
-From13.8to27.7turns=0.2%
-From27.7to10,000turns=0.1%
3-position selector to set the following
operation modes:
- LOCAL: for local control only
- OFF: no control is active but the actuator is
still connected to the mains
- REMOTE: for remote control only
Alphanumeric display: during normal
operation the alphanumeric display shows the
present status (NORMAL, ESD ON, ALARM,
WARNING,INTERLOCK),the3-position
selector status (LOCAL, OFF, REMOTE) and the
actuator action (OPEN, OPENING, CLOSED,
CLOSING, STOP or
R%:xxx.x).IfthelocalselectorisinOFFor
REMOTE, pressing the YES push-button it is
possible to scroll the list of variables, alarms
and reports:
CLOSE/NO
STOP
OPEN/YES
The ICON 2000 can be provided with a
radiofrequency wireless connection based on
a qualified Bluetooth™ class 1 module. This
allows to establish a connection and exchange
data with a PDA or PC with built-in Bluetooth™
technology. The following tasks can be
wirelessly performed:
- View and change configuration
- Set maintenance function
- Read maintenance data
- Download new firmware to the ICON 2000
- The blue LED indicates that the
communication with a host device is
established
Local controls: OPEN/YES, CLOSE/NO, and
STOP push-buttons.
The STOP push-button resets any existing
command and is active both in local and
remote.
If the 3-position selector is in LOCAL, the
OPEN / YES, and CLOSE /NO push-buttons
work as OPEN and CLOSE commands.
If the 3-position selector is in REMOTE or
in OFF, the OPEN / YES and CLOSE / NO
push-buttons work as YES and NO to answer
theprompt(next?OK?view?,change?exit?)of
the alphanumeric display.
In OFF, the OPEN / YES and CLOSE / NO
push-buttons allow to scroll down the menu,
to view and change the actuator configuration
or to scroll the list of variables, status, and
alarms.
In REMOTE, the above push-buttons allow
scrolling the list of variables, status, alarms
and reports but the actuator configuration
cannot be viewed or changed.
- actuator control
- actuator configuration
- actuator status visualisation
The figures on the following pages describe
the function of each component of the local
operator interface.
Three LED’s to indicate the actuator status
according to the following logic:
- green ON/ red OFF: the actuator is stopped in
open position
- green OFF/ red ON: the actuator is stopped in
closed position
- green OFF/ red flashing: the actuator is
running in closing direction
- green flashing/ red OFF: the actuator is
running in opening direction
- green ON/ red ON: the actuator is stopped in
intermediate position
- yellow ON: alarm
- yellow flashing: warning
The above color combination is supplied as
standard, but it may be changed (red with
green, green with red, and yellow with red),
during actuator setting operations.
1
3
2
4
5
6
output torque mot temp
motor speed term temp
main voltage log status
current wireless report
temperature node report *
time FDI report *
date base report
alarm term report
warning Ain/Aout report *
Ktemp
The data with * are only present if the relevant
modules are present.