6.3 ENTERING THE VIEW MODE
The existing actuator configuration should
be checked before commissioning. The
parameters are configured in factory
according to a standard setting, or to customer
requirements. In view mode, no password is
requested, but no change of parameters can
be made.
•Ensuretheelectricalmainpowerisapplied.
•Movethe3-positionselectortoOFFandthen
simultaneously press OPEN/YES and STOP.
•Thedisplayshowsthepresentlanguage.
Press YES to confirm or NO to scroll the list
of available languages. Press YES to select a
new language. Press YES to confirm.
•PressNOtoscrollthelistofavailablemenus
(actuator set-up, nameplate, valve data,
maintenance) and then press YES to select
the desired menu.
•PressNOtoscrollthelistofavailable
routines and press YES to select the routine
where the parameter to be changed is
located.
•PressNOtoscrollthelistofparametersand
press YES to view the value.
6.4 ENTERING THE SET-UP MODE
To change the existing settings or to set the
stroke limits it is necessary to enter the correct
password.
•Ensuretheelectricalmainpower(orthe
external auxiliary supply) is applied.
•Movethe3-positionselectortoOFFandthen
simultaneously press OPEN/YES and STOP.
•Thedisplayshowsthepresentlanguage.
Press YES to confirm or NO to scroll the list
of available languages. Press YES to select.
Press YES to confirm the chosen language.
•PressNOwhenthemessageis
“VIEWMODEOK?”.PressYEStoanswer
prompt“ENTERPASSWORDOK?”.
•Enterpassword.Enteronedigitatatime.
Press YES if digit is correct, press NO to
scroll the list of available characters and
then press YES when the character is
correct. Enter 4 digits. After entering the
last digit, the microprocessor checks the
password. If it is correct the messages
“PASSWORD CORRECT” and then
“SET-UPMODEOK?”appear.PressYES.
•PressNOtoscrollthelistofavailablemenus
(actuator set-up, valve data, maintenance)
and press YES to select the desired menu.
•PressNOtoscrollthelistofavailable
routines and press YES to select the routine
where the parameter to be changed is
located.
•PressYESandNOtoanswertheprompton
the display and change the parameter.
•Ifthepasswordiswrongthemessage
“PASSWORD WRONG” appears and set-up
mode will not available.
6.5 EXIT FROM VIEW AND SET-UP MODE
The following conditions cause the exit from
view and set-up mode:
•Movethe3-positionselectortoLOCALor
REMOTE.
•AnswerYESwhenthedisplayasks
“EXITOK?”.
•PressYESandNOsimultaneously.
•Automaticexitafter90minuteswithoutany
parameter change or view.
•Removetheelectricalpowerfromtheunit.
All settings are automatically saved to a
non-volatile memory and retained also if the
electrical power is removed from the actuator.
All ICON 2000 actuators are configured before
shipping with a standard default setting unless
alternatives were requested on order. In case
of difficulty during commissioning, the default
setting can be re-instated by the appropriate
function in the routine ”miscellaneous” of the
actuator set-up menu. The actuator returns to
its original configuration and commissioning
can be resumed.