31
BIFFI ICON 2000
InstructIon and operatIng manual
Configuration procedure
•MovethelocalselectortoOFFandthen
simultaneously press OPEN and STOP. Select
the language and then enter the password
according to the instructions (see “Entering
the set-up mode”). When the message
displayedis“SET-UPMODEOK?”press
YES. Press YES to select the actuator set-up
menu, press NO to scroll the list of available
routines and then press YES to select Local
controls.
•PressYEStochangecontrolmode,orpress
NO to proceed to LED’s color setting.
Control mode
•PressYESifthedisplayshowsthecorrect
control mode or press NO to scroll the list
of available options (push-to-run, latched).
Press YES to confirm.
Option "push-to-run rel. AS5-6" is used when
a remote enabling of local commands is
required. With the local selector in LOCAL,
pressing the OPEN or CLOSE local push-
buttons causes relays AS5 or AS6 to switch,
but no command is sent to motor. The
control PLC should read the status of the
above-mentioned relays and send an open
or close command on the remote inputs
(see paragraph 5.6, push-to-run mode; see
relevant electrical diagram when the option is
used).
LED’s color
•PressYESifthecoloroftheopenLEDis
correct. Press NO to change it, then YES to
confirm.
•PressYESifthecolorofthecloseLEDis
correct. Press NO to change it, then YES to
confirm.
•PressYESifthecolorofthealarmLEDis
correct. Press NO to change it, then YES to
confirm.
9.1.6 Output relays
Monitor relay
The voltage-free, change-over, contacts of the
monitor relay indicate that the actuator is either
available for remote control or that a problem
or a condition preventing remote control of the
valve exists.
The following situation can be configured
individually to switch-over the monitor relay:
- motor over-temperature
- over-torque
- jammed valve
- LOCAL/OFF selected
- manual operation
- ESD signal on (ESD-EFS)
- low lithium battery (if present)
- LOCAL/STOP pressed
The contacts may be configured to make
or break on condition. The options “EFS in
manual”, “EFS mid-travel” and “PST failed”
also appear in the menu, but are not available
for ICON 2000 v4.
Status
- open limit
- closed limit
-position>=xx%
-position<=xx%
- closing
- opening
- motor running
- blinker
- mid-travel position
- local selected
- remote selected
- local stop active
- ESD signal on
- manual operation
Alarm
- motor over-temperature
- over-torque
- over-torque in OP
- over-torque in CL
- valve jammed
- warnings
- valve jammed in OP
- valve jammed in CL
- low lithium battery (if present)
- mid travel alarm in CL/OP
- mains-only AS8
Auxiliary output relays
For status indication or diagnostic purposes,
8 voltage-free contacts of 8 relays are available
to be configured individually to switch for the
following conditions:
9.1.5 Local controls
This routine allows:
- To configure the control mode by means
of the local controls when the 3-position
selector is in LOCAL. The available options
are “push-to-run”, “latched”, “latched with
instant reverse”.
- To set the LED’s color. The following options
are available: open LED: green or red; close
LED: green or red; alarm LED: yellow or red.
The monitor relay is normally energized and
will be de-energized on:
- main voltage failure
- lost phase
- internal temperature alarm
-K1contactorfailure
-K2contactorfailure
- position sensor failure
- speed sensor failure
- configuration error
- HW error
- mid-travel alarm
Configuration procedure
•MovethelocalselectortoOFFandthen
simultaneously press OPEN and STOP.
Select the language and enter the password
according to the instructions (see “Entering
the set-up mode”). When the message
displayedis“SET-UPMODEOK?”press
YES. Press YES to select actuator set-up
menu, press NO to scroll the list of available
routines and then press YES to select Output
relays.
•PressYEStoselectDEFAULT#1,orpress
NO to change.
•PressYEStoselectDEFAULT#2,orpress
NO to configure the output relays.