UC***-18GS series
Description of Sensor Parameters
8.6.3 Error Replacement Value Current/Voltage
You can use this parameter to adjust which value the analog output should adopt in the event of
an error. Adjustment is possible in increments of 0.1 mA or 0.1 V.
The final value actually output at the analog output in the event of an error (current/voltage
value) depends on the setting of the "Output type" parameter for the analog output.
8.7 Sensor configuration Local controls
8.7.1 Local controls
You can use this parameter to set whether and in what period of time during operation of the
sensor local controls can be used to carry out changes.
By default, local controls are locked 5 minutes after switching on the power supply or after the
last access to the local controls (>> time locked (5 min)).
If the parameter is set to "Locked," the local controls are locked permanently.
By selecting "Unlocked," the local controls can be accessed at any time. You can always
change the sensor settings via the local controls.
Open This setting is only available for switching outputs. It sets the output
status to "Open" in the event of an error.
Replacement value This setting is only available for analog outputs. It specifies that in the
event of an error, a certain output value should be output at the analog
output. In the event of an error, this output value is determined via the
"Error replacement value current" or "Error replacement value volt-
age" parameter.
Parameter value Meaning
Note
To be able to adjust the replacement value, the "Replacement value" setting must be set to
"Output behavior if an error occurs" for the analog output in the DTM. Only the error
replacement value parameter appropriate to the analog output and the selected output type is
displayed ("Error replacement value current" or "Error replacement value voltage").
Parameter name Access Value range
Error replacement value cur-
rent
Read/write 0 ... 200 [x 0.1 mA]
Error replacement value
voltage
Read/write 0 ... 200 [x 0.1 V]
Table 8.35
Parameter name Access Value range
Programming button Read/write Locked
Time locked (5 min)
Unlocked
Table 8.36

Table of Contents

Other manuals for Pepperl+Fuchs UC-18GS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pepperl+Fuchs UC-18GS Series and is the answer not in the manual?

Pepperl+Fuchs UC-18GS Series Specifications

General IconGeneral
BrandPepperl+Fuchs
ModelUC-18GS Series
CategoryAccessories
LanguageEnglish

Related product manuals