UC***-18GS series
Maintenance and Repair
10 Maintenance and Repair
10.1 Maintenance Work
The sensor itself is maintenance-free. For this reason, it is not necessary to carry out regular
adjustments or maintenance work on the sensor itself.
However, check that the sensor and connector are tight within the scope of routine mainte-
nance intervals. You may also want to check that the connection cable is installed and intact.
10.2 Cleaning
Cleaning is only necessary in applications in which the transducer surface is exposed to dirt or
build-up.
In general, the following applies as far as cleaning is concerned:
Only with water without chemicals
Without pressure/high pressure
Only by using a soft cloth
No abrasive cleaning, scratching, or scrubbing
10.3 Resetting to the Factory Default
You can reset the sensor to the factory default setting in the following ways:
Using the programming button
Via the DTM in the Service menu
Via IO-Link
Resetting with the programming button
1.
Disconnect the sensor from the power supply.
2.
Press and hold the T programming button.
3.
Switch on the supply voltage. The yellow and red LEDs flash simultaneously for 5 seconds.
Then the yellow and green LEDs flash simultaneously for a further 5 seconds.
4.
Release the T programming button while the yellow and green LEDs flash simultaneously.
The sensor will now function with the original factory settings. If the T programming button
continues to be pressed down beyond this flash sequence, the sensor changes back to nor-
mal operation (green LED lights up). In this case, all settings remain unchanged in the sen-
sor.
The following graphic illustrates the sequence for the reset to factory settings:
Figure 10.1
T T
Power ON
. . .
. . .
5s
T
Normal operation
Normal operation
Exit
without
saving
Reset
hold button T
in total >10s
LED
red
yellow
LED
green
yellow
LED green
press and hold button T